EasyManuals Logo

HT EASYTEST COMBI519 User Manual

HT EASYTEST COMBI519
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
EASYTEST-COMBI519
EN - 91
10. TECHNICAL SPECIFICATIONS
Accuracy is calculated as: ±[%reading + (no. of digits) * resolution] at 23°C, <80%RH
10.1. TECHNICAL CHARACTERISTICS
AC TRMS voltage
Range [V] Resolution [V] Accuracy
15 460
1
(3%rdg + 2dgt)
Frequency
Range [Hz] Resolution [Hz] Accuracy
47.50 52.50 / 57.00 63.00
0.01
(
0.1%rd
g
+1d
g
t
)
Continuity of protective conductor (RPE)
Range [] Resolution []
Accuracy
0.00 9.99
0.01
(5.0rdg + 3dgt)
10.0 99.9
0.1
100 1999
1
Test current: >200mA DC up to 5 (test leads included)
Test current generated: 1mA resolution, range 0 ÷ 250mA
Open-circuit voltage: 4 < V
0
< 24VDC
Safety protection: error message for input voltage >10V
Insulation resistance (M)
Test voltage [V]
Range [M] Resolution [M]
Accuracy
50
0.01 9.99
0.01
(2.0rdg + 2dgt)
10.0 49.9
0.1
50.0 99.9 (5.0rdg + 2dgt)
100
0.01 9.99
0.01
(2.0rdg + 2dgt)
10.0 99.9
0.1
100 199
1
(5.0rdg + 2dgt)
250
0.01 9.99
0.01
(2.0rdg + 2dgt)
10.0 199.9
0.1
200 249
1
250 499 (5.0rdg + 2dgt)
500
0.01 9.99
0.01
(2.0rdg + 2dgt)
10.0 199.9
0.1
200 499
1
500 999 (5.0rdg + 2dgt)
1000
0.01 9.99
0.01
(2.0rdg + 2dgt)
10.0 199.9
0.1
200 1999
1
Open-circuit voltage rated test voltage -0% +10%
Rated measuring current: >1mA with 1k x Vnom (50V, 100V, 250V, 1000V), >2.2mA with 230k @ 500V
Short-circuit current <6.0mA for each test voltage
Safety protection: error message for input voltage >10V
Line/Loop impedance (Phase-Phase, Phase-Neutral, Phase-Earth)
Range [] Resolution []
Accuracy (*)
0.01 9.99
0.01
(5%rdg + 3dgt)
10.0 199.9
0.1
(*) 0.1m
in range 0.1
199.9 m
(by using the optional accessory IMP57)
Maximum test current: 3.31A (at 265V); 5.71A (at 457V)
P-N/P-P Test voltage: (100V 265V) / (100V460V); 50/60Hz ±5%
Protection types: MCB (B, C, D, K), Fuse (aM, gG, BS882-2,BS88-3, BS3036, BS1362)
First fault current – IT systems
Range [mA] Resolution [mA] Accuracy
0.1 0.9
0.1
(5rdg+1dgt)
1 999
1
(5rdg + 3dgt)
Limit contact voltage (ULIM) : 25V, 50V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HT EASYTEST COMBI519 and is the answer not in the manual?

HT EASYTEST COMBI519 Specifications

General IconGeneral
BrandHT
ModelEASYTEST COMBI519
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals