EASYTEST-COMBI519
EN - 44
7.
In case of a positive result (all tripping times comply
with what indicated in 12.4) of all the test sequentially
performed, the “OK” message is shown and the screen
to the side is displayed by the instrument.
RCD
15/10 – 18:04
TN
0° 180°
X1 38ms 35ms
X5 22ms 27ms
X½ >999ms >999ms
FREQ=50.00Hz Ut=0.0V
VL-N=232V VL-PE=231V
OK
AUTO 30mA
MODE
In
Type Ut
8. Press the SAVE key to store the test result in the instrument’s memory (see § 7.1) or
the ESC/MENU key to exit the screen without saving and go back to the main
measuring screen.
6.6.2. AUTO
mode
5.
Press the GO/STOP key on the instrument, the START
key on the remote switch probe or use the AutoStart
feature (see § 5.1.5). The instrument will start the
measurement.
RCD
15/10 – 18:04
TT 0° 180°
--- mA --- mA
X1 --- ms --- ms
X5 --- ms --- ms
X½ --- ms --- ms
FREQ.=50.0Hz Ut = - - - V
VL-PE= 231V VL-N = 232V
Measuring...
AUTO 30mA
MODE
In
Type Ut
CAUTION
If message “Measuring…” appears on the display, the instrument is
performing measurement. During this whole stage, do not disconnect the
test leads of the instrument from the mains.
6.
The AUTO
mode provides for the automatic execution
of 8 measurements in a sequence:
(Ramp) with phase 0° (the RCD must trip, reset
the switch, message “Resume RCD” is shown)
(Ramp) with phase 180° (the RCD must trip, reset
the switch, message “Resume RCD” is shown)
IdN x 1 with phase 0° (the RCD must trip, reset the
switch, message “Resume RCD” is shown)
IdN x 1 with phase 180° (the RCD must trip, reset
the switch, message “Resume RCD” is shown)
IdN x 5 with phase 0° (the RCD must trip, reset the
switch, message “Resume RCD” is shown)
IdN x 5 with phase 180° (the RCD must trip, reset
the switch, message “Resume RCD” is shown)
IdN x½ with phase 0° (RCD must not trip)
IdN x½ with 180° (RCD must not trip, end of test)
RCD
15/10 – 18:04
TT 0° 180°
23 mA --- mA
X1 --- ms --- ms
X5 --- ms --- ms
X½ --- ms --- ms
FREQ.=50.0Hz Ut = - - - V
VL-PE= 231V VL-N = 232V
Resume RCD.
AUTO 30mA
MODE
In
Type Ut

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HT EASYTEST COMBI519 and is the answer not in the manual?

HT EASYTEST COMBI519 Specifications

General IconGeneral
BrandHT
ModelEASYTEST COMBI519
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals