EASYTEST-COMBI519
EN - 56
4. The value of the test leads/mains plug resistance is
maintained by the instrument up to the reset operation
performed by the user (for example, for the insertion of
cables with different lengths).
To reset the saved calibration value, remove the
ZEROLOOP accessory and press the GO/STOP key. The
” symbol disappears and the screen to the side
appears on the display.
LOOP 15/10 – 18:04
TN
RL
RN
RPE
=
=
=
- - -
- - -
- - -
FREQ. = 0.00Hz
VL-PE=0V
VL-N=0V
Zero reset
CAL
FUNC