EASYTEST-COMBI519
EN - 93
Overall earth resistance without RCD tripping (Ra )
Voltage range P-PE, P-N: 100V 265V
Voltage range N-PE: <10V
Frequency: 50/60Hz 5%
Overall earth resistance in systems with Neutral (3-wire) – (30mA or higher RCD)
Range [] Resolution []
Accuracy
0.05 9.99
0.01
(5rdg +8dgt)
10.0 199.9
0.1
Overall earth resistance in systems with Neutral (3-wire) – (6mA and 10mA RCD)
Range [] Resolution []
Accuracy
0.05 9.99
0.01
(5rdg +30dgt)
10.0 199.9
0.1
Overall earth resistance in systems withot Neutral (2-wire) – (30mA or higher RCD)
Range [] Resolution []
Accuracy
0.05 9.99
0.01
(5rdg +8dgt)
10.0 99.9
0.1
100 1999
1
Overall earth resistance in systems withou Neutral (2-wire) – (6mA and 10mA RCD)
Range [] Resolution []
Accuracy
0.05 9.99
0.01
(5rdg +30dgt)
10.0 99.9
0.1
100 1999
1
Contact voltage (measured during RCD and Ra test)
Range [V] Resolution [V] Accuracy
0 Ut LIM
0.1
-0%, +(5.0 rdg + 3V)
Phase rotation with 1 test lead
Voltage range P-N, P-PE[V] Frequency range
100 265 50Hz/60Hz 5%
Measurement is only carried out by direct contact with metal live parts (not on insulation sheath).