Cascade Address
Cascade Number
Range: 00 (Master), 01 (follower 1), …., 19 (follower 19) Default: 00
NOTE: “28:cP” needs to be set on the Master boiler with total number of
cascaded units before setting “27: cn”
NOTE: The Master boiler must always be addressed 00.
28:cP
01
Cascade Parameter
Total number of cascaded units (Set on cascade Master boiler ONLY.)
NOTE: 28:cP will not appear on Follower boilers once it has been selected on
the Master.
Range: 01 20 (Default: 01)
29:Eh
OFF
Common Vent
Common Vent
Range: ON / OFF
30:Cr
Cr:at
Auto
Automatic rotation (default)
The first unit to operate when there is a T/T call is the unit that ran the least
amount of time during the prior heat calls (burner ON time).
Cr:Ct
48
Cascade Rotation time
Cascade Rotation time
Range: 0-240 Hours
31:CT
180F
Cascade System temperature
Cascade System temperature:
Range: 95F 180F
32:Cd
10 F
Cascade System Temperature
Differential (burner ON)
Cascade System Temperature Differential (burner ON)
Range: 5-30 F
33:HA
HA 0
High Elevation Mode
High Elevation Mode (0-2, 2-5, 5-8, 8-10)
34:AP
AP:cP
5
CH System Pump and DHW
Indirect Pump Test Mode
This function sets the time to run Boiler pump, CH System pump or DHW
Indirect pump to purge air from the system. Range: 1 30 minutes
cP1:Off
or
cP1:On
OFF
Boiler and CH System Pumps Test
Mode
Turn this function on to activate Boiler pump and CH System pump.
Only works in installation mode. Turns off when in normal mode.
cP2:Off
or
cP2:On
OFF
DHW Indirect Pump Test Mode
Turn this function on to activate DHW Indirect pump.
Only works in installation mode. Turns off when in normal mode.
35:SS
SS:Sd
OFF
OFF
Allows the user to set the date of next service reminder
XX / XX / XXXX (MONTH / DAY / YEAR)
A wrench will be displayed on the display panel when the service is due.
YEAR
MON
Allows the user to set the year of
next service reminder
DATE
SS:br
00
Allows the user to set the service
reminder based on BURNER RUN
HOURS
Allows the user to set the service reminder based on BURNER RUN HOURS
A clock will be displayed on the display panel when the service is due.
Range: 00 indexing to 9,999 hours
NOTE: Two digits will appear initially. As you scroll to the right more digits will
appear.
36:UC
FAH(F)
FAH(F)
Allows the user to change the
unit
Allows the user to change the unit
Range: F or C
CEL(C)
37:CM
OFF
CH Step Modulation
Allows the user to turn ON the step modulation, which regulates burner output
in six steps at one minute intervals. Step modulation will start at the last
modulation rate of the boiler and work up one minute at a time. Default: OFF
(Selection: OFF or ON).
38:dM
OFF
DHW Step Modulation
39:SA
AquA
Aquastat
An aquastat or indirect sensor can be used when using an indirect water
heater. Range: AquA or SEnS. Default: AquA
NOTE: If an aquastat is used and SEnS is selected, the boiler will not operate
and Er.32 will display. If a sensor is used and AquA is selected, the boiler will
not operate. No error will display.
SEnS
Sensor
Table 23 Installer Mode Descriptions
H. ERROR MODE
The following screen will display when the boiler encounters an error. The boiler control is able to record information about the boiler’s
condition at the time of the ten previous faults or errors. This information is available to view in the Installer Mode under the History
screen.
Figure 42 Error Mode Screen

Table of Contents

Other manuals for HTP UFT-100W

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HTP UFT-100W and is the answer not in the manual?

HTP UFT-100W Specifications

General IconGeneral
BrandHTP
ModelUFT-100W
CategoryBoiler
LanguageEnglish

Related product manuals