EasyManuals Logo

HTP UFT-100W User Manual

HTP UFT-100W
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #55 background imageLoading...
Page #55 background image
55
LP-542 REV. 7.16.15
Figure 47 Outdoor Reset Curve See Installer Mode for Curve Setting Descriptions
K. 0-10 VOLT INPUT
1. A signal from a building management system may be connected to the boiler to enable remote control. This signal should be a 0-10
volt positive-going DC signal. When this input is enabled, a building control system can be used to control the set point temperature of
the boiler. The control interprets the 0-10 volt signal as follows; when the signal is between 0 and 1.5 volts, the boiler will be in standby
mode, not firing. When the signal rises above 1.5 volts, the boiler will ignite. As the signal continues to rise towards its maximum of 10
volts, the boiler will increase in set point temperature.
2. Connect a building management system or other auxiliary control signal to the terminals marked for this purpose on the boiler
terminal block (shown in Piping Diagrams, this manual). Caution should be used to ensure that the 0-10 VOLT + connection does not
become connected to ground.
NOTE: Ensure that the polarity of the connections from the external modulating boiler controller to the boiler is correct. Reversed
polarity could lead to erratic and/or no response from the boiler controller.
NOTE: Outdoor Temperature Mode Icon on the display will flash if an Outdoor Sensor or 0-10 Volt is not connected to the boiler.
0-10 V INPUT TABLE:
When outside voltage is applied to the connector (2) in the wiring diagram,
1. The Outdoor temperature sensor does not work.
2. Symbol is displayed.
3. The heating temperature is automatically set according with the external voltage input.
NOTE: 0-10V is prioritized over T/T. If input voltage is less than 1.5V then T/T will operate.
The range of input voltage is approximately 1.5[V] ~ 10[V] and the heating temperature settings according to this range are as follows.
Input voltage[V]
Heat temperature []
Heat temperature []
1.5
30.0
86
2.0
32.7
91
2.5
36.1
97
3.0
38.8
102
9.0
75.0
167
9.5
77.7
172
10
82.2
180
Table 26 0-10V Input Voltages and Associated Temperatures

Table of Contents

Other manuals for HTP UFT-100W

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HTP UFT-100W and is the answer not in the manual?

HTP UFT-100W Specifications

General IconGeneral
BrandHTP
ModelUFT-100W
CategoryBoiler
LanguageEnglish

Related product manuals