FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Power distribution circuit
breakers for IT equipment
40 A/1P x 18 x 2; 63 A/1P x 6 x 2
2000 mm x 600 mm x 1100 mm
2000 mm x 600 mm x 1200 mm (with a tail frame)
2200 mm x 600 mm x 1200 mm (with a top frame and tail
frame)
An integrated UPS cabinet works in 380 V, 400 V, or 415 V power mode, and features
redundancy, high reliability, high efficiency, energy saving, environmental protection, and
intelligent and easy operation.
Table 3-8 lists the technical specifications for the integrated UPS.
Table 3-8 Technical specifications for the integrated UPS
380 V, 400 V, or 415 V AC, three-phase,
four-wire, and PE
80–280 V AC (phase voltage) (When the input
voltage ranges from 80 V AC to 176 V AC,
loads are linearly derated.)
> 0.99 (full load); > 0.98 (50% load)
380 V, 400 V, or 415 V AC, three-phase,
four-wire, and PE
Total harmonic
distortion (THD)
(linear load)
Total harmonic
distortion (THD)
(non-linear load)
Maximum peak factor
for loads
3:1 (in compliance with IEC 62040-3 standard)
60 min (105%–110% load)
10 min (111%–125% load)
1 min (125%–150% load)
30 to 40 12 V batteries (32 batteries by default)
Derated by 6% when 30 batteries are used