FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Battery strings are shared in the cabinet by
default. There are no combined cabinets in the
Smart Module.
Equalized charging voltage: 2.35 V/cell; float
charging voltage: 2.25 V/cell
The maximum battery capacity is 3,000 Ah.
The charging current is limited based on the
battery capacity.
Number of combined
cabinets
In a Smart Module, cabinets do not need to be
combined.
Routed in and out from the top
The integrated UPS supports the 3+1 working
mode (three power modules and one redundant
module) and supports up to 112 kW IT cabinet
power. IT cabinet power can be 32 kW (1+1),
72 kW (2+1), or 112 kW (3+1).
At atmospheric pressure (25ºC)
⚫
25% load: 54 dB
⚫
50% load: 58 dB
⚫
75% load: 61 dB
⚫
100% load: 65 dB
Maintained from the front or rear
ATS (Optional)
Table 3-9 lists the specifications of an ATS.
Table 3-9 ATS specifications
187–264 V AC (phase voltage)