Alarm
ID
Alarm Name Alarm
Severity
Possible Cause Troubleshooting
3051 ESS Version Mismatch Major
1. The version of the
battery power control
modules does not
match that of the
battery packs, which
aects the normal
operation.
2. The update failed.
1. The version of the
power control
modules in [Battery-
CabinetNo] does not
match that of the
battery packs and
needs to be updated.
2. If the update fails
multiple times,
contact your dealer or
technical support.
3061 Battery Pack Lifespan
Reached
Major The battery has
reached its lifespan.
The battery has
reached the end of its
lifespan. Contact the
local recycling agency
to dispose of it in
compliance with local
laws and regulations
as well as applicable
standards.
8.4 Battery Storage and Recharge
Battery Acceptance Inspection
A battery recharge label must be put on the battery packing case. The recharge
label should contain the latest charge time and the next recharge time.
Battery Storage Requirements
1. Place batteries according to the signs on the packing case during storage. Do
not put batteries upside down or sidelong.
2. Stack battery packing cases by complying with the stacking requirements on
the external package.
3. Handle batteries with caution to avoid damage.
4. The storage environment requirements are as follows:
Ambient temperature: -10–55°C; recommended storage temperature: 20–
30°C
Relative humidity: 5% to 80%
Place batteries in a dry and clean place with proper ventilation.
Place batteries in a place that is away from corrosive organic solvents and
gases.
Keep batteries away from direct sunlight.
LUNA2000-(5-30)-S0
User Manual 8 System Maintenance
Issue 15 (2024-01-12) Copyright © Huawei Digital Power Technologies Co., Ltd. 129