Parameter Description
Communication
disconnection
fail-safe
● Disable
● Enable
In the inverter anti-backfeeding
scenario, if this parameter is set to
Enable, the inverter will derate
according to the active power
derating percentage when the
communication between the inverter
and the Dongle is disconnected for a
period longer than Communication
disconnection detection time.
Communication
disconnection
detection time
- Species the time for determining
the communication disconnection
between the solar inverter and the
Dongle.
Active power
output limit for
fail-safe
- Species the derating value of the
inverter active power by percentage.
If the Dongle does not detect any
meter data or the communication
between the Dongle and the inverter
is disconnected, the Dongle delivers
the derating value of the inverter
active power by percentage.
----End
Scenario 2: SmartLogger1000A Networking Scenario
See the
SmartLogger1000A User Manual
.
You can scan the QR code to obtain it.
SUN2000-(3KTL-10KTL)-M0
User Manual C Setting Export Limitation Parameters