SUN2000L-(4.125KTL, 4.95KTL)-JP
User Manual
8 System Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
119
Alarm ID
Alarm
Name
Alarm
Severity
Possible Cause
Suggestion
2032
Grid
Failure
Major
Cause ID = 1
The power grid experiences
an outage.
The AC circuit is
disconnected or AC switch
is off.
1. Check the AC voltage.
2. Check that the AC power cable is
connected and that the AC switch
is ON.
2033
Grid
Undervolt
age
Major
Cause ID = 1
The grid voltage is below the
lower threshold or the low
voltage duration has lasted for
more than the value specified
by LVRT.
1. If the alarm occurs accidentally,
the power grid may be abnormal
temporarily. The SUN2000L
automatically recovers after
detecting that the power grid
becomes normal.
2. If the alarm occurs frequently,
check whether the grid voltage is
within the acceptable range. If no,
contact the local power operator.
If yes, modify the power grid
overvoltage and undervoltage
protection thresholds with the
consent of the local power
operator.
3. If the fault persists for a long
time, check the connection
between the AC switch and the
output power cable.
2034
Grid
Overvolta
ge
Major
Cause ID = 1
The grid voltage exceeds the
higher threshold or the high
voltage duration has lasted for
more than the value specified
by HVRT.
1. Check whether the grid
connection voltage exceeds the
upper threshold. If yes, contact
the local power operator.
2. If you have confirmed that the
grid connection voltage exceeds
the upper threshold and obtained
the consent of the local power
operator, modify the overvoltage
and undervoltage protection
thresholds.
3. Check whether the peak grid
voltage exceeds the upper
threshold.
2035
Unbalance
d Grid
Voltage
Major
The difference between grid
phase voltages exceeds the
upper threshold.
1. Check that the grid voltage is
within the normal range.
2. Check the connection of the AC
output power cable.
3. If the cable connection is proper
but the alarm occurs frequently
and affects the power production
of the PV plant, contact the local
power operator.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000L Series and is the answer not in the manual?

Huawei SUN2000L Series Specifications

General IconGeneral
Max. DC Voltage600 V
Max. Efficiency98.6%
CoolingNatural Convection
Protection DegreeIP65
Power Output Range2kW - 5kW
Max. AC Power5, 500 VA
Rated AC Voltage220 V / 230 V
European Efficiency98.2%
Operating Temperature Range-25°C to +60°C
Weight10.6 kg
CommunicationRS485