SUN2000L-(4.125KTL, 4.95KTL)-JP
User Manual
7 Operations on the Local FusionHome App
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
92
Parameter
Description
Value Range
Comm interruption duration
(min)
Specifies the duration for
determining communication
interruption. Used for
automatic shutdown for
protection in case of
communication interruption.
[1, 120]
Soft start time (s)
Specifies the duration for
the power to gradually
increase when the
SUN2000L starts.
[20, 1800]
OFF due to abnormal
grounding
This function is used to
detect whether the
SUN2000L is properly
grounded before starting the
SUN2000L, or to detect
whether the ground cable is
disconnected when the
SUN2000L is working. This
parameter is set to Enable
by default. For certain types
of power grids, if an
isolation transformer
connects to the output side
of the SUN2000L, you need
to set OFF due to
abnormal grounding to
Disable after checking that
the SUN2000L is properly
grounded. Then the
SUN2000L can start
normally.
If you are not sure whether
the SUN2000L connects to
such a power grid, confirm
it with your dealer or
Huawei technical support.
Disable
Enable
Delay upgrade
This parameter is mainly
used in the upgrade
scenarios where the PV
power supply is
disconnected at night due to
no sunlight or unstable at
dawn or dusk due to poor
sunlight.
Disable
Enable