7
to interrupt the system for a prescribed period of time set 
by the interrupt delay position on the dial.
The system startup delay and interrupt period can be 
adjusted by moving the dials on the Flow-Clik Interface Box 
to the desired settings. The system startup delay allows 
for system stabilization to occur prior to the Flow-Clik 
sensing for an overflow condition. The startup delay can be 
adjusted from 0 to 300 seconds.
The interrupt period setting allows the user to program the 
Flow-Clik to shut the system off for a prescribed amount of 
time. The interrupt period can be adjusted by moving the 
dial to a specified setting from 5 to 60 minutes. There is 
also a Restart Manually position on the dial that shuts the 
system off until it is manually restarted at the Interface Box.
In the following example, the startup delay is set for 20 
seconds and the interrupt period is set to 10 minutes. 
High-Flow Scenario 1 – Valve 3 Lateral Line Breaks
If a lateral line break should occur on valve number 3, the 
Flow-Clik would sense a “high flow” condition and would 
shut the system down after a sustained 20 second over 
flow condition. Once the system has been shut off, the 
Flow-Clik will continue to keep the system off for the 10 
minutes programmed into the interrupt period. After 10 
minutes have passed, the Flow-Clik will turn the system 
back on and begin to monitor for an over flow condition.
If the run time for zone 3 is 19 minutes and is scheduled 
to come on at 6:00 am, then the following chain of events 
would occur:
6:00 AM – Valve 3 is activated and the Flow-Clik senses an 
over flow condition. After a 20 second delay the system is 
shut off for 10 minutes.
6:10 AM – Valve 3 is reactivated (it still has 9 minutes of 
run time left) and after a 20 second delay, a “high flow” 
condition is again identified and the system is interrupted 
for another 10 minutes.
6:18 AM – Valve 4 is scheduled to be activated by the 
irrigation controller, however, the Flow-Clik continues to 
interrupt system operation due to the 1 minute left on the 
interrupt delay.
6:20 AM – Valve 4 is activated and the Flow-Clik begins to 
monitor the flow of valve 4 which is below the “high flow” 
trigger point enabling the controller to continue to irrigate 
as it normally would.