** Only Comfort - DS/Comfort Plus - DS
*** Hy, C = Electrode Steam Generator, HL = Heater Element Steam
Generator
X
Light / sparks in the
cylinder
The appearance of light or sparks suggests
rapid loss of electrode material (brown-black
deposits) and very high water conductivity.
In these cases, consult HygroMatik.
Blow-down pump is not working properly or is
defective.
Deactivate the unit immediately to
prevent it from being damaged.
Perform maintenance:
- Replace electrodes
- Clean steam cylinder
- Check water quality or
conductivity, also see Section „Di-
rections for Use“.
Increase blow-down frequency
and/or blow-down volume.
Check blow-down pump function
and replace blow-down pump if
necessary. See message Blow-
Down Fault
HL ***
Hy,C***
Possible Condi-
tions
Probable Cause for fault situation Resolution
* :