Table 5. SPCN Error Codes (continued)
Error Code Description Action/
Possible Failing FRU
1031 1524 Power supply 2 cooling fault 1. I/O drawer power supply 2
Location: U0.3-V2
2. Secondary I/O backplane
Location: U0.3-P1
1031 1526 Power supply 2 missing I/O drawer power supply 2
Location: U0.3-V2
1031 1B01 Load fault on +12 1. I/O drawer power supply
Location: U0.3-V1
2. If power supply U0.3-V2 is present (no
cooling unit), use the power supply you
removed from U0.3-V1 to replace
U0.3-V2
3. Secondary I/O backplane
Location: U0.3-P1
1031 1B02 Load fault on +5 1. I/O drawer power supply
Location: U0.3-V1
2. If power supply U0.3-V2 is present (no
cooling unit), use the power supply you
removed from U0.3-V1 to replace
U0.3-V2
3. Secondary I/O backplane
Location: U0.3-P1
1031 1B03 Load fault on +3.3 1. I/O drawer power supply
Location: U0.3-V1
2. If power supply U0.3-V2 is present (no
cooling unit), use the power supply you
removed from U0.3-V1 to replace
U0.3-V2
3. Secondary I/O backplane
Location: U0.3-P1
1031 1B04 Load fault on -12 1. I/O drawer power supply
Location: U0.3-V1
2. If power supply U0.3-V2 is present (no
cooling unit), use the power supply you
removed from U0.3-V1 to replace
U0.3-V2
3. Secondary I/O backplane
Location: U0.3-P1
1031 1B05 Load fault on 1.8 1. I/O drawer power supply
Location: U0.3-V1
2. If power supply U0.3-V2 is present (no
cooling unit), use the power supply you
removed from U0.3-V1 to replace
U0.3-V2
3. Secondary I/O backplane
Location: U0.3-P1
182 Service Guide