Table 5. SPCN Error Codes (continued)
Error Code Description Action/
Possible Failing FRU
1031 1B06 Load fault on 2.5 1. I/O drawer power supply
Location: U0.3-V1
2. If power supply U0.3-V2 is present (no
cooling unit), use the power supply you
removed from U0.3-V1 to replace
U0.3-V2
3. Secondary I/O backplane
Location: U0.3-P1
1031 1B07 Load fault on 2.5 1. I/O drawer power supply
Location: U0.3-V1
2. If power supply U0.3-V2 is present (no
cooling unit), use the power supply you
removed from U0.3-V1 to replace
U0.3-V2
3. Secondary I/O backplane
Location: U0.3-P1
1031 2600 Pgood fault Secondary I/O backplane
Location: U0.3-P1
1031 2601 Pgood fault Secondary I/O backplane
Location: U0.3-P1
1031 2603 Secondary I/O drawer power domain fault 1. Check input power to power supplies
Locations: U0.3-V1
U0.3-V2
2. I/O drawer power supplies
Locations: U0.3-V1
U0.3-V2
3. I/O Drawer Power Distribution Board
Location: U0.3-X1
4. Secondary I/O backplane
Location: U0.3-P1
1031 2612 SPCN problem Secondary I/O backplane
Location: U0.3-P1
1031 3100 I2C controller fault 1. Secondary I/O drawer operator panel
Location: U0.3-L1
2. Secondary I/O backplane
Location: U0.3-P1
1031 3101 I2C bus 1 fault Secondary I/O backplane
Location: U0.3-P1
1031 3102 I2C bus 2 fault Secondary I/O backplane
Location: U0.3-P1
1031 3104 I2C bus 4 fault Secondary I/O backplane
Location: U0.3-P1
1031 3105 I2C bus 5 fault 1. Fan controller card
Location: U0.3-X2
2. Secondary I/O backplane
Location: U0.3-P1
3. I/O drawer power distribution board
Location: U0.3-X1
1031 3113 RIO bus adapter fault RIO bus adapter
Location: U0.3-P1.1
Chapter 5. Error Code to FRU Index 183