30 PRT-CTRL-SE Protege SE Integrated System Controller Installation Manual | June 2017
8.2 Defaulting a Controller
The Controller can be set back to factory default using the following procedures. This resets all internal data and
event information.
Step 1
Remove power from the controller by disconnecting the AC and battery supply.
Step 2
Turn ON configuration dip switch 4.
Step 3
Power up the Controller by turning on the AC supply.
Step 4
Turn OFF configuration dip switch 4 once the Controller is indicating normal status by flashing the green status
indicator. The system will now be defaulted with all programming and settings returned to factory configuration.
i
Defaulting the Controller does not reset the IP address. To reset an IP address, refer to the details on
the Configuration Switch (see page 29).