PRT-CTRL-SE Protege SE Integrated System Controller Installation Manual | June 2017 41
Validation
In order to comply with UL1610 and UL1635 72 hr standby requirements, is
the Total Output Current less or equal to 60mA?
Yes, it is 30mA
Is the DC Output (AUX1) current less or equal to 1.0A (1000mA)? Yes, it is 30mA
Is the total combined current less or equal to 1.7A (1700mA)? Yes, it is 0.5A (500mA)
13.5 Current and Validation (UL Installation) Example 2
Using a 100VA Transformer and 14Ah Battery
UL294 (4 hr standby capacity)
External Devices Connected to Panel
2 x PRX-NPROX Nano Prox Card Readers (120mA @ 13.8VDC) connected on AUX2 Outputs
2 x Electric Locking Devices (520mA @ 13.8VDC)
Standby Current Consumption
Total Output Current Available 2A (2000mA)
DC Output (AUX2) PRX-NPROX Nano Prox Card Reader (120mA @ 13.8VDC)
DC Output (AUX2) PRX-NPROX Nano Prox Card Reader (120mA @ 13.8VDC)
B1 Output Electric Locking Device (520mA @ 13.8VDC)
B2 Output Electric Locking Device (520mA @ 13.8VDC)
Total Output Current Consumption 1.28A (1280mA)
Current Consumption
Total Combined Current Available 2.5A (2500mA)
Operating Current 120mA (Typical)
Battery Charging 700mA (High Current Charging)
DC Output (AUX2) PRX-NPROX Nano Prox Card Reader (120mA @ 13.8VDC)
DC Output (AUX2) PRX-NPROX Nano Prox Card Reader (120mA @ 13.8VDC)
B1 Output Electric Locking Device (520mA @ 13.8VDC)
B2 Output Electric Locking Device (520mA @ 13.8VDC)
Total Consumption 2.1A (2100mA)