EasyManua.ls Logo

ICT Protege SE - Page 42

ICT Protege SE
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42 PRT-CTRL-SE Protege SE Integrated System Controller Installation Manual | June 2017
Validation
In order to comply with UL294 4 hr standby requirements, is the Total
Output Current less or equal to 2A?
Yes, it is 1.28A (1280mA)
Is the DC Output current (AUX2) less or equal to 1.0A (1000mA)? Yes, it is 240mA
Is B1 current output less or equal to 1.1A (1100mA)? Yes, it is 520mA
Is B2 current output less or equal to 1.1A (1100mA)? Yes, it is 520mA
Is the total combined current less or equal to 2.5A (2500mA)? Yes, it is 2.1A (2100mA)

Table of Contents

Related product manuals