SECTION 2 - INSTALLATION
Installation and Servicing
37
Pump Modulation
The boiler is factory set for 70% minimum
CH pump speed. This can be increased
to 100%. Press “Enter” and the following
screen will be displayed:
Press “next” until the following screen is
displayed:
Press “Enter” and the following screen will
be displayed:
Press “Change” to change the setting.
Press “Exit to return to normal operation.
Outside Sensor Slope
This feature is only accessible if an outside
sensor has been tted to the boiler. Boiler
performance can be adjusted relative to
the insulation level of the building. To
change the slope press “Menu” and the
following screen will be displayed:
Press “Next” until the following screen is
displayed:
Press “Enter” and the following screen will
be displayed.
Press “Change” until the desired setting is
displayed.
Note. The slope is active for settings
between 5 and 40. Default is 17.
Press “Exit” to return to normal operation.
Diverter Valve Mid Position
To move the diverter valve to the mid
position, ensure there are no demands
for heat and press “Menu”. The following
screen will be displayed:
Press “next” until the following screen is
displayed:
Press “Enter” and the diverter valve will
move to mid position and the following
screen will be displayed:
Press “Exit to return to normal operation.
MENU OPERATIONS
Outside Sensor Slope
Diverter Valve Mid Position
Exit
Diverter Valve Mid Position