FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
C
OMMUNICATION
M
ANUAL
FC9Y-B1730 11-9
11: W
EB
S
ERVER
Batch Monitor
In the batch monitor, 200 consecutive data registers can be monitored and controlled with the specified data type.
Operation procedure
1. In Device Number, specify the device number to monitor.
200 consecutive data registers starting with the specified data register are monitored. The valid device numbers are 0 to 7800,
8000 to 8300, and 10000 to 49800. If an invalid value is entered, the value is corrected automatically.
2. Select the Monitor Type to display the data registers in the desired format.
Data register values are shown in the format specified by the monitor type. See the web data type for the available data types.
3. Click on a cell in which data register value is shown.
A dialog box to write a data is shown. The entered value is written to the FC6A Series MicroSmart.