Function Specifications
■ CPU Module Performance
*1 1 step is equivalent to 8 bytes.
*2 There are limitations on the maximum number of outputs that can be simultaneously turned on.
For details, see "Connection Restrictions When Expanding the PLC" on page 3-37.
*3 A maximum of three cartridges can be used by connecting the cartridge base module and HMI module.
*4 The maximum number of expansion modules that can be connected can be increased by using the expansion interface module. For details, see
"Expansion Interface Modules" on page 2-143.
Backup Function
*1 D70000 to D269999 cannot be designated as "Keep." Data register values are kept when you switch the PLC from Stop to Run, but those values
are cleared at power up.
*2 To prepare for when the battery dies, the contents of RAM (internal relays, shift registers, counters, and data registers) can be saved to non-
volatile memory. For how to save the contents of RAM, see "SD Memory Card" on page 11-1.
*3 The battery is primarily consumed by backup current while unpowered. However, the ambient environment (temperature and humidity) while
unpowered and powered also affects consumption. In particular, battery life is greatly reduced in a high-temperature and high-humidity
environment, so replacement is recommended every year when the effect of the ambient environment (temperature and humidity) while
unpowered and powered is included.
*4 Replacement while powered and replacement while power is supplied from the USB bus are also possible. For the replacement method, see
"Replacing the Backup Battery" on page 3-34.
Type No.
FC6A-D16R1CEE, FC6A-D16R4CEE
FC6A-D16K1CEE, FC6A-D16K4CEE
FC6A-D16P1CEE, FC6A-D16P4CEE
FC6A-D32K3CEE, FC6A-D32K4CEE
FC6A-D32P3CEE, FC6A-D32P4CEE
Program
Capacity
*1
Program Data
800,000 bytes
(100,000 steps)
Comment Data 384,000 bytes
I/O Expansion
Basic Expansion 7
Expansion Interface 8
Cartridges
*3
3
I/O Points
Basic
Input 816
Output 816
Basic Expansion
*2
224
Expansion Interface
*4
256
Cartridges
*3
12
Expanded I/O with Expansion Interface
Remote Master/Slave Modules
I/O in the system can be expanded up to a maximum of 63 modules using expansion
interface modules (remote master/slave) (I/O points: maximum 2,016 points). For details,
see "Expansion Interface Modules (Remote Master/Slave)" on page 2-146.
User Program Download 1,000 times
Control System Stored program system
Instructions
Basic Instructions 42 type
Advanced Instructions 124 type
Processing
Speed
Basic Instruction 0.021 ms/1,000 steps
END Processing 1 ms
Internal Relay 15,400
Shift Register 256
Data Register 60,000
Counter (adding, reversible) 512
Timer (1 ms, 10 ms, 100 ms, 1 s) 2,000
Backup Data RAM (internal relays, shift registers, counters, data registers
*1
)
*2
, clock
Backup Battery
Lithium ion primary cell (A battery is included with the product. The model of battery to be
included with the product cannot be specified.)
Panasonic: BR2032/CR2032A/CR2032B, Murata: CR2032X/CR2032W
Battery Life Guaranteed 1 year, replacement recommended every 4 years (+25°C)
*3
Replaceability Replace within 1 minute after power off (recommended)
*4