10.2.3 Limit monitoring OUT1 or OUT2 / window function
Select [uni�F] and set the unit of measurement�
Select [SELx] and set FLOW�
Select [oux] and adjust the switching signal:
- Fno = window function / normally open
- Fnc = window function / normally closed
Select [FHx] and set the upper limit of the window section�
Select [FLx] and set the lower limit for the window section�
Menu OUTx:
[SELx]
[oux]
[FHx]
[FLx]
10.2.4 Analogue signal volumetric flow OUT2
Select [uni�F] and set the unit of measurement�
Select [SEL2] and set FLOW�
Select [ASP2] and set the value at which 4 mA is provided�
Select [AEP2] and set the value at which 20 mA is provided�
Menu OUT2:
[SEL2]
[ou2]
[ASP2]
[AEP2]
10.3 Settings for consumed quantity monitoring
10.3.1 Quantity monitoring by pulse signal OUT1 or OUT2
Select [uni�F] and set the unit of measurement�
Select [SELx] and set FLOW�
Select [oux] and adjust the pulse output: ImP
Select [ImPSx] and set pulse value (= volumetric flow quantity at which
a pulse is provided):
1� Press [▲] or [▼] to select the setting range�
2� Briefly press [
] to confirm the setting range�
3� Press [▲] or [▼] to set the requested numeric value�
4� Briefly press [
] to apply the value�
Select [ImPRx] and set YES�
Menu OUTx:
[SELx]
[oux]
[ImPSx]
[ImPRx]
10.3.2 Quantity monitoring by preset counter OUT1 or OUT2
Select [uni�F] and set the unit of measurement�
Select [SELx] and set FLOW�
Select [oux] and adjust the pulse output: ImP
Select [ImPSx] and set the volumetric flow quantity at which output x
switches�
Select [ImPRx] and set NO�
Menu OUTx:
[SELx]
[oux]
[ImPSx]
[ImPRx]