17
18
80
mm
18
Area with intense snowfalls (natural drain)
Ice can build up when using the air conditioner in central heating
mode. During de-icing, the condensate water must be drained
safely. For the air conditioner to work properly, follow the in-
structions below.
- Leave more than 80 mm between the bottom of the outdoor unit
and the ground for the installation (see gure 17).
- If the product is installed in a region with heavy snowfalls, leave
sucient space between the product and the ground (see gure
18).
- When you install the product, make sure that the mount is not
positioned below the drain hole.
- Make sure that the drain water ows out correctly and safely.
Snow-proof roof
Frame
Ground
Estimated snowfall
ATTENTION:
- in zones subject to heavy snowfalls,
the snow buildup could block in the
air vents. To avoid this occurrence, install
a frame higher than the estimated level of
the snow. Furthermore install a snow-proof
roof to prevent the snow from piling up on
the outdoor unit.
- In zones subject to snowfalls, do not install
the discharge outlet and the drain plug in the
outdoor unit. ey could make the ground
freeze. erefore, take appropriate measures
to prevent it.