7. Description of Parameters MD500 User Manual
- 122 -
Ƶ
Pulse Reference (DI5)
7KHIUHTXHQF\UHIHUHQFHLVLQSXWE\PHDQVRI',KLJKVSHHGSXOVH7KHVLJQDOVSHFLILFDWLRQRISXOVHUHIHUHQFHLVWR9
(voltage range) and 0 to 100 kHz (frequency range). The corresponding value 100% of the pulse reference corresponds to the value
of F0-10 (Max. frequency).
Note
The main frequency reference set via pulse reference and the pulse output of
the FM terminal (F5-00 = 1) cannot be used simultaneously.
F4-28 to F4-32 set the relationship between the pulse input (from DI5 only) and the corresponding percentage. It has the same
function and usage as the AI curve 1 does. Refer to the description of AI curve 1.
Function Code Parameter Name Setting Range Default
F4-28 Pulse min. input 0.00 kHz to F4-30 0.00 kHz
) Corresponding percentage
of pulse min. input
-100.00% to 100.0% 0.0%
F4-30 Pulse max. input F4-28 to 50.00 kHz 50.00
kHz
F4-31 Corresponding percentage
of pulse max. input
-100.00% to 100.0% 100.0%
F4-32 3XOVHÀOWHUWLPH 0.00s to 10.00s 0.10s
)LJXUH3XOVHLQSXWDW',WRFRQWUROIUHTXHQF\UHIHUHQFH
Note:
100.0% corresponds to max. frequency (F0-10).
DI5
F4-04 = 30
Use pulse signals to
control frequency
reference (valid for
DI5 only)
COM
Final
frequency
reference
Select main frequency
reference as final
frequency reference.
OC
output
Set the relationship between the
pulse input (from DI5 only) and the
corresponding percentage via F4-28
to F4-32.
F0-03
F0-03 = 5
Select pulse as main
frequency reference
setting channel.
F0-07
(Unit's digit) = 0