7.3.1 Start Mode
You can set the start mode of the AC drive in F6-00, direct start, catching a spinning motor and pre-excited start.
The related function parameters are listed as follows:
Function Code Parameter Name Setting Range Default
F6-00 Startup mode 0: Direct start
1: Catching a spinning motor
2: Pre-excited start
0
F6-01 Mode of catching a
spinning motor
0: From stop frequency
1: From zero speed
2: From max. frequency
0
F6-02 Speed of catching a
spinning motor
1 to 100 20
F6-03 Start frequency 0.00 to 10.00 Hz 0.00 Hz
F6-04 Start frequency holding time 0.0s to 100.0s 0.0s
F6-05 '&LQMHFWLRQEUDNLQJOHYHO
Pre-excitation level
0% to 100% 0%
F6-06 '&LQMHFWLRQEUDNLQJDFWLYH
WLPH3UHH[FLWDWLRQDFWLYHWLPH
0.0s to 100.0s 0.0s
ƕ F6-00 = 0: Direct start
It is applicable to most loads, as shown in Figure 6-30 (1).
The start with start frequency (F6-03) is applicable to the hoist application, such as elevator and crane, as shown in Figure
6-30 (2).
7KHVWDUWZLWK'&LQMHFWLRQEUDNLQJIXQFWLRQLVDSSOLFDEOHWRWKHDSSOLFDWLRQZKHUHWKHPRWRUPD\URWDWHDVVKRZQLQ)LJXUH
6-30 (3).
Figure 7-30 (1) Timing diagram of direct start
Acceleration time
Output frequency
Start command