MD500 User Manual 5. Quick Setup
- 71 -
5.2 Setup Flowchart
START Para. Parameter name Default Commission
Before power on
Check voltage of power supply Bear in mind that if a higher voltage power supply than necessary is connected
to inverter, then inverter will probably get damaged instantly, for example 380V
SRZHUVXSSOLHVWRD9FODVVLQYHUWHUWKHQUHFWLÀHUEULGJHZLOOJHWEXUQW
So please check it before power on with a reliable instrument.
Check wirings If we wrongly connect power supply to inverter, then
inverter will probably get damaged instantly.
If any one of inverter outputs keeps short-circuited to ground all
the way, then inverter may get damaged sooner or later, though
protective algorithm is planted inside. Motor windings being short-
circuited between phases or to ground may also be damaging.
of power supply and inverter outputs
Restore parameters FP-01 Parameter operation 0
0: No operation
1: Restore default settings except motor parameters
2: Clear records including errors
4: Restore users backup parameters
501: Backup parameters
NOTE: usually people have no idea what parameters have
been changed, so it’s seriously recommended to restore
parameters to default at the beginning of commissioning.
Set motor parameters Motor Nameplate
F1-01 Rated motor power model dependent
Unit: kW
F1-02 Rated motor voltage model dependent
Unit: V
F1-03 Rated motor current model dependent
Unit: A
F1-04 Rated motor frequency model dependent
Unit: Hz
F1-05 Rated motor speed model dependent
Unit: rpm.
CONTINUE Para. Parameter name Default Commission