MD500 User Manual 7. Description of Parameters
7.11 Auxiliary Function
7.11.1 Jog
-RJLVUHTXLUHGWRWHVWWKHHTXLSPHQW,QWKHMRJUXQQLQJ)PXVWEHVHWWRGLUHFWVWDUWDQG)PXVWEHVHWWR'HFHOHUDWH
to stop).
Function Code Parameter Name Setting Range Default
F0-25 $FFHOHUDWLRQ'HFHOHUDWLRQ
time base frequency
0: Maximum frequency (F0-10)
1: Frequency reference
2: 100 Hz
0
F8-00 Jog frequency reference 0.00 Hz to maximum frequency 2.00 Hz
F8-01 Jog acceleration time 0.0s to 6500.0s 20.0s
F8-02 Jog deceleration time 0.0s to 6500.0s 20.0s
Jog acceleration time indicate the time required by the AC drive to accelerate from 0 Hz to F0-25.
Jog deceleration time indicate the time required by the AC drive to decelerate from F0-25 to 0 Hz.
Function Code Parameter Name Setting Range Default
F8-27 Selection of terminal
MRJRYHUULGLQJ
0: Disabled
1: Enabled
0
7KLVIXQFWLRQSDUDPHWHUGHWHUPLQHVZKHWKHUWHUPLQDOMRJRYHUULGHVRWKHUFRPPDQGV,IWKLVIXQFWLRQLVHQDEOHGWKH$&GULYHZLOO
VZLWFKRYHUWRWKHMRJUXQQLQJVWDWHZKHQDQ\RI)WR)LVVHWWRIRUZDUGMRJRUUHYHUVHMRJ
Figure 7-60 Jog running
F8-01
Time (t)
Output frequency
F0-25
Set acceleration time
Set deceleration time
Actual acceleration time
Actual deceleration time
F8-02
F8-00
Jog command
)ROORZWKHVWHSVEHORZWRFRQWUROWKHGULYHMRJYLDWKHRSHUDWLRQSDQHO
Steps )RUZDUGMRJ 5HYHUVHMRJ
1 6HW) WRDOORFDWHWKH0).NH\ZLWKWKHIRUZDUGMRJ
function.
6HW) WRDOORFDWHWKH0).NH\ZLWKWKHUHYHUVHMRJ
function.
Set F8-13 = 0 to allow reverse running.
2 Set F0-02 = 0 to select the operation panel as the command
source.
Set F0-02 = 0 to select the operation panel as the command
source.
3 Set F8-00, F8-01 and F8-02 properly. Set F8-00, F8-01 and F8-02 properly.
4
In the drive stop state, press down the
MF.K
key. Then the AC
GULYHVWDUWVWRMRJLQWKHIRUZDUGGLUHFWLRQ$IWHU\RXUHOHDVHWKH
MF.K
key, the AC drive decelerates to stop.
In the drive stop state, press down the
MF.K
key. Then the AC
GULYHVWDUWVWRMRJLQWKHUHYHUVHGLUHFWLRQ$IWHU\RXUHOHDVHWKH
MF.K
key, the AC drive decelerates to stop.