7. Description of Parameters MD500 User Manual
- 162 -
For example, the application requires report of Err11 when the motor runs at 150% of rated motor current for two minutes.
According to Figure 7-47, 150% (I) is in the range of 145% (I1) and 155% (I2). 145% corresponds to the overload protection time 6
minutes (T1) and 145% corresponds to the overload protection time 4 minutes (T2). You can calculate the overload protection time
T corresponding to 150% from the following formula:
7 777[,,,, [ PLQXWHV
7KHQ\RXFDQFDOFXODWHWKHPRWRURYHUORDGSURWHFWLRQJDLQIURPWKHIROORZLQJIRUPXOD)'HVLUHGRYHUORDGSURWHFWLRQWLPH
&RUUHVSRQGLQJRYHUORDGSURWHFWLRQWLPH  
Note
6HW)SURSHUO\DFFRUGLQJWRWKHDFWXDORYHUORDGFDSDFLW\RIWKHPRWRU,IWKHVHWWLQJLVWRRODUJH
the AC drive may not report Err11 timely when the motor is damaged due to overheating.
Function Code Parameter Name Setting Range Default
) Motor overload pending
FRHIÀFLHQW
50% to 100% 80%
The AC drive has the motor overload pending function that reminds of motor overload in advance through the digital output
function 6.
2QWKHFRQGLWLRQWKDW)DQG)ZKHQWKHPRWRUUXQQLQJFXUUHQWUHDFKHVRIUDWHGPRWRUFXUUHQWDQGWKH
motor runs at this level for 80% x 6 = 4.8 minutes, the DO terminal or the fault relay outputs the motor overload pending signal.
:KHQ) WKHPRWRURYHUORDGSHQGLQJDQGWKHPRWRURYHUORDGSURWHFWLRQDUHSHUIRUPHGVLPXOWDQHRXVO\
7.6.2 Phase Loss Protection
Function Code Parameter Name Setting Range Default
) Selection of power input phase
ORVVFRQWDFWRUFORVHSURWHFWLRQ
0: Disabled
1: Enabled
11
Unit's digit: Power input phase loss protection
Ten's digit: Contactor close protection
This function parameter determines whether to perform power input phase loss or contactor close protection.
Function Code Parameter Name Setting Range Default
) Power output phase
loss protection
0: Disabled
1: Enabled
1
This function parameter determines whether to perform power output phase loss protection. If the protection is disabled but power
output phase loss occurs, the AC drive does not report the fault. This moment, the actual current is larger than the panel displayed
current.