MD500 User Manual 7. Description of Parameters
- 177 -
)LJXUH7KHÀ[HGOHQJWKFRQWUROVFKHPDWLFGLDJUDP
DI5
DIx
Allocate DI5 with the length signal
pulses counting function.
F4-04 = 27
Any of F4-04
to F4-= 28
Allocate DIx with the
length reset function.
=
Fb-06
Actual length
Fb-05
Set length
Clear to 0
Compare
DO
Any of F5-00
to F5-05 = 10
Reset
Allocate DO with the
length reached function.
DO outputs the length
reached signal.
Length reset input
Length reached output
Length pulses input
1 2 3 10 11 12
1 2
Fb-06 = 0
Fb-06 = 11
Fb-05 = 11
U0-13 = 0
Number of sampled pulses Fb-
07 (Number of pulses per meter)
7KHVHWWLQJVRIUHODWHGIXQFWLRQSDUDPHWHUVLQWKHSUHFHGLQJÀJXUHDUHDVIROORZV
Function Code Parameter Name Setting Description
F4-04 DI5 function selection 27 Length pulses counting input
$Q\RI)WR) DIx function selection 28 Length reset
Any of F5-00 to F5-05 DOx function selection 10 Length reached
Note
ƕ Only the length can be calculated according the number of pulses but the rotation
GLUHFWLRQZLOOQRWEHREWDLQHGLQWKHÀ[HGOHQJWKFRQWUROPRGH
ƕ An automatic stop system can be implementing by connecting the output
length reached signal of the relay to the stop input terminal.