MD500 User Manual 7. Description of Parameters
- 187 -
2. Flexible connection
)RUWKHPDVWHULQVSHHGFRQWUROSHUIRUPWKHIROORZLQJVHWWLQJV1RWHWKDWRQO\WKHVHWWLQJRI)FDQEHPRGLÀHG
Function Code Parameter Name Setting Range Setting
Fd-00 Baud rate WR Keep the thousand's digit of this
parameter to the same value
for the master and slave.
A8-00 Selection of point-point
communication
0: Disabled
1: Enabled
1
A8-01 Master and slave selection 0: Master
1: Slave
0
F0-10 Max. frequency 5.00 to 500.00 Hz 50.00 Hz
Keep the same setting of this
parameter for the master and slave.
F8-15 Droop rate 0.00 to 10.00 Hz 1.00 Hz
F0-17 Acceleration time 1 0.0 to 6500.0s Keep the same setting of this
parameter for the master and slave.
F0-18 Deceleration time 1 0.0 to 6500.0s Keep the same setting of this
parameter for the master and slave.
)RUWKHVODYHLQVSHHGFRQWUROSHUIRUPWKHIROORZLQJVHWWLQJV1RWHWKDWRQO\WKHVHWWLQJRI)FDQEHPRGLÀHG
Function Code Parameter Name Setting Range Setting
Fd-00 Baud rate WR Keep the thousand's digit of this
parameter to the same value
for the master and slave.
A8-00 Selection of point-point
communication
0: Disabled
1: Enabled
1
A8-01 Master and slave selection 0: Master
1: Slave
1
A8-02 Selection of action of the slave
in point-point communication
000 to 111
0: No
1: Yes
Unit's digit: Whether to follow
the master's command
1
Ten's digit: Whether to send
fault information to the master
when a fault occurs on it
1
Hundred's digit: Whether to
DODUPZKHQLWEHFRPHVRIÁLQH
-
A8-03 Selection of purpose of
the slave received data
0: Torque reference
1: Speed reference
1
F0-02 Command source selection 0: Operation panel control (LED off)
1: Terminal control (LED on)
2: Communication control
/('ÁDVKLQJ
2