7. Description of Parameters MD500 User Manual
Function Code Parameter Name Setting Range Default
A8-07 Master data sending cycle in
point-point communication
0.001s to 10.000s
0.001s
This function parameter sets the data sending cycle of the master in point-point communication.
Function Code Parameter Name Setting Range Default
A8-08 Zero offset of received
data (frequency)
-100.00% to 100.00%
0.00%
$ Gain of received data (frequency)
-10.00 to 10.00
1.00
These two function parameters correct the received frequency data.
Function Code Parameter Name Setting Range Default
A8-10 5XQDZD\SUHYHQWLRQFRHIÀFLHQW
0.00% to 100.00%
10.00%
This parameter is valid only when the slave is in torque control and follows the master output torque to perform load allocation.
This function enables detection of slave runaway. If it is set to 0.00%, the runaway prevention function is disabled. The
recommended setting is 5.00% to 20.00%.
Function Code Parameter Name Setting Range Default
A8-11 Window width
0.20 to 10.00 Hz
0.5 Hz
This function parameter is effective only for the master and slave control mode. Modify the setting to ensure synchronization of
the master and slave speed within the window width.