9. Peripherals and Options MD500 User Manual
- 256 -
Type Terminal Terminal Name Function Description
Indicators
D4 in red Power supply indicator
ON: indicates that the drive is powered on.
OFF: indicates that the drive is not powered
on or the DP card is installed improperly.
D3 in yellow
DP card and master
communication indicator
ON: indicates normal communication
between the DP card and the master.
OFF: indicates no communication between the
DP card and the master (check the PROFIBUS
cable connection and station No. setting).
Flashing: indicates that the master does
not operate or wrong communication
between the DP card and the master.
D2 in green
DP card and drive
communication indicator
ON: indicates normal communication
between the DP card and the drive.
OFF: indicates that communication between the DP
card and the drive fails (check the baud rate setting).
Flashing: indicates that interference exists on the
communication between the DP card and the drive or the
extension card address is not within the rang of 1 to 125.
7KHIROORZLQJWDEOHGHVFULEHVWKHMXPSHUVRIWKH0''3
Jumper Description Meaning Setting
J6
CANlink terminal resistor
matching selection
Matching the terminal resistor
Not matching the terminal resistor
Description of DIP Switch and Address Setting
DIP Switch Bit Function Description
1 to 8
The PROFIBUS-DP communication
slave address
The 8-bit binary DIP switch can set state addresses of 0 to 125.
For example:
Address DIP switch setting
0 00000000
7 00000111
20 00010100
125 01111101
Note