MD500 User Manual 9. Peripheral and Options
- 271 -
Ƶ
EMC Guidance
ƕ Never bundle the encoder cables and the power cables together. Failure to comply will result in encoder interference.
ƕ The motor housing must be connected to the grounding terminal of the AC drive. Meanwhile, connect the grounding cable of
the motor to the motor housing reliably.
ƕ An STP cable is suggested. For differential encoders, perform cable connection based on the differential pairs properly and
connect the shield to the grounding terminal of the AC drive.
ƕ For large equipment application where the AC drive is far away from the motor and the motor cable is longer than 10 m, the
JURXQGLQJHIIHFWLVQRWJRRGGXHWRWKHLQÁXHQFHRIFDEOHLQGXFWDQFH,QWKLVFDVHWKHHQFRGHUVKLHOGQHHGQRWEHFRQQHFWWKH
grounding terminal of the AC drive.