Loading...
MD500 User Manual 13. EMC
- 303 -
Ƶ
Installing Fuse on the Input Side
To prevent accidents caused by short circuit, install fuse on the input side and the fuse must comply with the UL standard.
6HOHFWWKHIXVHDFFRUGLQJWRWKHIROORZLQJÀJXUH
MD500 Model FWH Series Fuse
Manufacturer: Bussmann
Rated Current Model
MD500T18.5G 80 FWH-80B
MD500T22G 100 FWH-100B
MD500T30G 100 FWH-100B
MD500T37G 125 FWH-125B
MD500T45G 150 FWH-150B
MD500T55G 200 FWH-200B
MD500T75G 250 FWH-250B
0'7* 275 FWH-275B
MD500T110G 325 FWH-325B
MD500T132 400 FWH-400B
MD500T160 500 FWH-500B
MD500T200 600 FWH-600B
MD500T220 700 FWH-700B
MD500T250 800 FWH-800B
MD500T280 800 FWH-800B
MD500T315 1000 FWH-1000B
MD500T355 1000 FWH-1000B
MD500T400 1200 FWH-1200B
Ƶ
3UHYHQWLQJ(QWU\RI)RUHLJQ2EMHFWV
7KH0'XQLWVPXVWEHLQVWDOOHGLQDÀUHSURRIFDELQHWZLWKGRRUVWKDWSURYLGHHIIHFWLYHHOHFWULFDODQGPHFKDQLFDOSURWHFWLRQ7KH
installation must conform to local and regional laws and regulations, and to relevant IEC requirements.
Ƶ
Grounding
If using an AC drive of the 400 V class, tie the neutral point of the drive power supply to ground.
efesotomasyon.com

Table of Contents

Related product manuals