Chapter 5 Function Code Table
- 46 -
Function
Code
Parameter Name Setting Range Default
Min.
Unit
Property
F4-01
Door close startup
acceleration time
0.1–999.9s 1.0s 0.1s
☆
F4-02
Low speed running time for
door close startup in speed
control
0.1–999.9s 1.0s 0.1s
☆
F4-03 Door close normal speed 0.00 Hz to F1-04 12.00 Hz
0.01
Hz
☆
F4-04 Door close acceleration time 0.1–999.9s 2.0s 0.1s
☆
F4-05 Door close ending low speed 0.00 Hz to F4-03 2.00 Hz
0.01
Hz
☆
F4-06 Door close deceleration time 0.1–999.9s 1.5s 0.1s
☆
F4-07 Door close limit low speed 0.00 Hz to F4-03 1.00 Hz
0.01
Hz
☆
F4-08
Low speed running time at
door close limit
0–9999 ms 300 ms 1 ms
☆
F4-09 Door vane retraction speed 0.00 to F4-03 2.00 Hz
0.01
Hz
☆
F4-10
Door vane retraction running
time
0–9999 ms 500 ms 1 ms
☆
F4-11
Torque switchover threshold
at door close limit
0.0%–150.0% 50.0% 0.1%
☆
F4-12
Door close limit holding
torque
0.0%–150.0% 30.0% 0.1%
☆
F4-13 Door close hindered torque 0.0%–150.0% 100.0% 0.1
★
F4-14
Working mode upon door
close hindered
0: Reserved
1: Output door close
hindered signal
2: Immediate stop
3: Door re-open
1 1
★
F4-15
Door close hindered judging
time
0–9999 ms 500 ms 1 ms
☆
F4-16
Door close normal speed at
re emergency
5.00 to F1-04 10.00 Hz
0.01
Hz
☆
F4-17
Normal speed at door close
hindered
F4-18 to F1-04 12.00 Hz
0.01
Hz
☆
F4-18
Low speed at door close
hindered
0.00 Hz to F1-04 2.00 Hz
0.01
Hz
☆
F4-19 Normal speed torque 0.00%–150.0% 100.0% 0.1%
☆
F4-20 Low speed torque 0.00%–150.0% 100.0% 0.1%
☆
Group F5: Door Open/Close Auxiliary Parameters
F5-00
Abnormality deceleration
time
0.1–5.0s 0.3s 0.1
☆