Optidrive HVAC User Guide V2.00
Optidrive HVAC Start Up Guide
OPTIDRIVE HVAC (IP20 Enclosure).
AC Supply Connection Supply Voltage
3 Phase Units : Connect L1 L2 L3, PE 200 240 Volts + / - 10%
1 Phase Units : Connect L1, L2, PE 380 380 Volts + / - 10%
Fuses or MCB
o Check the Technical Data in section 11 on page 47
Help Card
Display Information can be found in section 5.4 on page 26
Keypad Operation can be found in section 5.2 on page 25
IMPORTANT!
Hardware Enable Circuit
Link the terminals as shown, optionally through contacts to enable drive
operation
Control Terminals
Based on the factory default parameter settings
Run Stop 10K Speed Pot
Close the switch to run (enable), open to stop
Motor Cable
o For correct cable size see Technical Data on page 47
o Observe the maximum permissible motor cable length
o For Motor cable lengths > 50 metres, an output filter is
recommended
o Use a screened (shielded cable)
Motor Connection
o Check for Star or Delta connection according to the motor
voltage rating - see section 4.5 on page 23
o Motor Nameplate Details
o Motor Rated Voltage : P1-07
o Motor Rated Current : P1-08
o Motor Rated Frequency : P1-09
o Motor Rated Speed (Optional) : P1-10
Fuses or MCB