User manual of EC160 elevator intelligent integrated machine Function parameters
120
stopping floor
L0 parallel and group
control setting
T0 time setting
F0 function setting
U0 calling signal
U1 system monitoring
U2 hoistway
information
17 Entire running
protection time
18 Single floor running
protection time
Function
code
Instruction Setting rangedefault value Remarks
T0_00 Open delay 0~500s3
Not modify
in running
T0_00 sets the time from door open to automatic closing.
Function
code
Instruction Setting rangedefault value Remarks
T0_02 Return to the home floor delay 0~5000s120
Not modify
in running
T0_02 sets the time from the free elevator to returning to the home floor.
Function
code
Instruction Setting rangedefault value Remarks
T0_03 Free energy-saving delay 0~5000s60
Not modify
in running
T0_03 sets the time from free elevator to entering into the energy-saving state.
Function
code
Instruction Setting rangedefault value Remarks
T0_04 Brake opening delay 0~5.000s0.2
Not modify
in running
T0_05 Brake closing delay 0~5.000s0.4
T0_04: the time from running direction reference to the output brake
T0_05: the time from speed cancel to the brake cancel