User manual of EC160 elevator intelligent integrated machine Function parameters
121
Function
code
Instruction Setting range【default value】 Remarks
T0_06 Starting shake prevention delay 0~5.000s【0.3】
Not modify
in running
T0_06 sets the time from lock connection to the running contactor output.
Adjust the parameter when the door shakes when door closed.
Function
code
Instruction Setting range【default value】 Remarks
T0_07 Direction cancel delay 0~5.000s 【0.2】
Not modify
in running
T0_07 sets the time from detecting brake travel switch feedback after closing brake output to
canceling direction.
Adjust the parameter when the brake travel switch is not sensitive.
Function
code
Instruction Setting range【default value】 Remarks
T0_08 Inspection stopping delay 0~5.000s【0.300】
Not modify
in running
Set the time from brake cancel to direction cancel in inspection state. Increase the parameter
when the brake travel switch is not connected.
Valid when the parameter is more than or equal to 0.300, otherwise the
brake and speed will cancel in inspection stopping.
Function
code
Instruction Setting range【default value】 Remarks
T0_09 Fire running delay 0~5.000s【0.000】
Not modify
in running
Set the time from elevator forced stop to the fire floor entering into the fire state.