Goodrive270 series VFD for fan and pump Function parameter list
-164-
Function
code
Name Description Default
Modify
P06.14 AO1 output
0: Running frequency (0±Max. output frequency)
1: Set frequency (0
±Max. output frequency)
2: Ramp reference freque
ncy (0±Max. output
frequency)
3: Rotational speed (0
±Speed corresponding to
max. output frequency)
4: Output (0
±Twice the VFD rated current)
5: Output current (0
±Twice the motor rated
current)
6: Output (0
±1.5 times the VFD rated voltage)
7: Output power (
0±
Twice the motor rated power)
8: Set torque (0
±Twice the motor rated torque)
9: Output torque (Absolute value, 0
±±Twice the
motor rated torque)
10: AI1 input (0
±10V/0±20mA)
11: AI2 input (0
±10V)
12: AI3 input (0
±10V/0±20mA)
13: HDIA input (0.00
±50.00kHz)
14: Value 1 set through Modbus communication
(0
±1000)
15: Value 2 set through Modbus communication
(0
±1000)
16: Value 1 set through
PROFIBUS
/CANopen/DeviceNet (0±1000)
17: Value 2 set through
PROFIBUS
/CANopen/DeviceNet (0±1000)
18: Value 1 set through Ethernet communication
(0
±1000)
19: Value 2 set through Ethernet communication
(0
±1000)
20: Reserved
21: Value 1 set through EtherCAT/PROFINET
communication (0
±1000)
22: Torque current (bipolar, 0
±Triple the motor
rated current)
23: Exciting current (bipolar,
0±Triple the motor
rated current)
24: Set frequency (bipolar, 0
±Max. output
frequency)
25: Ramp reference frequency (bipolar, 0
±Max.
output frequency)
0 ƻ
P06.15 AO0 output 0 ƻ
P06.16 Reserved