Goodrive270 series VFD for fan and pump Function parameter list
-170-
Function
code
Name Description Default
Modify
P07.19 VFD rated voltage
50
±1200V
Model
depended
ƽ
P07.20 VFD rated current
0.1
±6000.0A
Model
depended
ƽ
P07.21
Factory bar code 1
0x0000±0xFFFF
ƽ
P07.22
Factory bar code 2
0x0000±0xFFFF
ƽ
P07.23
Factory bar code 3
0x0000±0xFFFF
ƽ
P07.24
Factory bar code 4
0x0000±0xFFFF
ƽ
P07.25
Factory bar code 3
0x0000±0xFFFF
ƽ
P07.26
Factory bar code 4
0x0000±0xFFFF
ƽ
P07.27
Present fault type
0: No fault
1: Inverter unit U
-phase protection (OUt1)
2: Inverter unit V
-phase protection (OUt2)
3: Inverter unit W
-phase protection (OUt3)
4: Overcurrent during acceleration (OC1)
5: Overcurrent during deceleration (OC2)
6: Overcurrent during constant speed running
(OC3)
7: Overvoltage
during acceleration (OV1)
8: Overvoltage during deceleration (OV2)
9: Overvoltage during constant speed running
(OV3)
10: Bus undervoltage fault (UV)
11: Motor overload (OL1)
12: VFD overload (OL2)
13: Phase loss on input side (SPI)
14: Phase loss on outpu
t side (SPO)
15: Rectifier module overheat (OH1)
16: Inverter module overheat (OH2)
17: External fault (EF)
18: RS485 communication fault (CE)
19: Current detection fault (ItE)
20: Motor autotuning fault (tE)
21: EEPROM operation error (EEP)
22: PID feedba
ck offline fault (PIDE)
23: Braking unit fault (bCE)
24: Running time reached (END)
ƽ
P07.28
Last fault type
ƽ
P07.29
2nd-last fault type
ƽ
P07.30
3rd-last fault type
ƽ
P07.31
4th-last fault type
ƽ
P07.32 5th-last fault type ƽ