Goodrive270 series VFD for fan and pump Function parameter list
-196-
Function
code
Name Description Default
Modify
0: Coast to stop
LED tens place: Inverter module overheat (same
as that for ones place)
LED hundreds place: External fault
0: Coast to stop
1: Stop according to the stop mode
2: Pre
-alarm and run
3: Keep running
LED thousands place: RS485 communication
fault (same as that for hundreds place)
P11.33
Fault protection
selection 3
0x0000
±0x3100
LED ones place: Current detection fault
0: Coast to stop
LED tens place: Motor autotuning fault (same as
that for ones place)
LED hundreds place: EEPROM operation fault
0: Coast to stop
1: Stop according
to the stop mode
LED thousands place: PID feedback offline
0: Coast to stop
1: Stop according to the stop mode
2: Pre
-alarm and run
3: Keep running
0 ƻ
P11.34
Fault protection
selection 4
0x0000
±0x1311
Ones place: Braking unit overheating
0: Coast to sto
p
1: Stop according to the stop mode
Tens place: Running time reached (same as that
for ones place)
0: Coast to stop
1: Stop according to the stop mode
Hundreds place: Electronic overload
0: Coast to stop
1: Stop according to the stop mode
2: Pre
-alarm and run
3: Keep running
Thousands place: Keypad communication fault
(same as that for ones place)
0 ƻ