Goodrive270 series VFD for fan and pump Function parameter list
-197-
Function
code
Name Description Default
Modify
P11.35
Fault protection
selection 5
0x0000
±0x0300
Ones place: Keypad upload fault
0: Coast to stop
Tens place: Keypad download fault (same as
that for ones place)
Hundreds place: DP communication fault
0: Coast to stop
1: Stop according to the stop mode
2: Pre
-alarm and run
3: Keep running
Thousands place: Reserved
0 ƻ
P11.36
Fault protection
selection 6
0x0000
±0x3003
Ones place: CANopen communication fault
0: Coast to stop
1: Stop according to the stop mode
2: Pre
-alarm and run
3: Keep running
Tens pla
ce: To-ground short-circuit fault 1
0: Coast to stop
Hundreds place: To
-ground short-circuit fault 2
(same as that for tens place)
Thousands place: Speed deviation fault (same
as that for ones place)
0 ƻ
P11.37
Fault protection
selection 7
0x0000
±0x0011
O
nes place: Mal-adjustment fault
0: Coast to stop
1: Stop according to the stop mode
Tens place: Electronic underload fault (same as
that for ones place)
Hundreds place: Reserved
Thousands place: Reserved
0 ƻ
P11.38
Fault protection
selection 8
Reserved
P11.39
Fault protection
selection 9
Reserved
P11.40
Fault protection
selection 10
Reserved