Goodrive270 series VFD for fan and pump Function parameter list
-198-
Function
code
Name Description Default
Modify
P11.41
Fault protection
selection 11
Reserved
P11.42
Fault protection
selection 12
0x0000
±0x3303
Ones place: Duplicate expansion card type
0: Coast to stop
1: Stop according to the stop mode
2: Pre
-alarm and run
3: Keep running
Tens place: Reserved
Hundreds place: PROFINET communication
timeout fault (same as that for ones place)
Thousands place: CAN communication fault
(same as that for ones place)
0 ƻ
P11.43
Fault protection
selection 13
0x0000
±0x0333
Ones place: Motor overheating
0: Coast to stop
1: Stop according to the stop mode
Tens place: Failed to identify the expansion card
in card slot 1
0: Coast to stop
1: Stop according to the stop mode
2:
Pre-alarm and run
3: Keep running
Hundreds place: Failed to identify the expansion
card in card slot 2 (same as that for tens place)
Thousands place: Reserved
0 ƻ
P11.44
Fault protection
selection 14
0x0000
±0x0033
Ones place: Communication timeout of
expa
nsion card at card slot 1
0: Coast to stop
1: Stop according to the stop mode
2: Pre
-alarm and run
3: Keep running
Tens place: Communication timeout of
expansion card at card slot 2 (same as that for
ones place)
Hundreds place: Reserved
Thousands place: Reserved
0 ƻ

Table of Contents