Goodrive270 series VFD for fan and pump Function parameter list
-199-
Function
code
Name Description Default
Modify
P11.45
Fault protection
selection 15
0x0000
±0x0300
Ones place: Reserved
Tens place: Reserved
Hundreds place: CAN slave fault in master/slave
synchrization
0: Coast to stop
1: Stop according to the stop mode
2: Pre
-alarm and run
3: Keep running
Thousands place: Reserved
0 ƻ
P11.46
Fault protection
selection 16
0x0000
±0x3300
Ones place: Reserved
Tens place: Reserved
Hundreds place: Freezing fault
0: Coast to stop
1: Stop according to the stop mode
2: Pre
-alarm and run
3: Keep running
Thousands place: Stal
ling fault (same as that for
hundreds place)
0 ƻ
P11.47
Fault protection
selection 17
0x0000
±0x0003
Ones place: Dry pumping
0: Coast to stop
1: Stop according to the stop mode
2: Pre
-alarm and run
3: Keep running
Tens place: Reserved
Hundreds place: Reser
ved
Thousands place: Reserved
0 ƻ
P11.48
Fault protection
selection 18
0x0000
±0x0000
Reserved
P11.49
Fault protection
selection 19
0x0000
±0x0000
Reserved
P11.50
Fault protection
selection 20
0x0000
±0x0000
Reserved
P11.51
Output frequency
selection for running
0x0000
±0x0004
Ones place:
0 ƻ