Goodrive200A inverters Function parameters
36
Function
code
Name Detailed instruction of parameters
Default
value
Modify
frequency. And then, the inverter will run from the
starting frequency to the set frequency. If the set
frequency is lower than the starting frequency,
the inverter will stop running and keep in the
stand-by state. The starting frequency is not
limited in the lower limit frequency.
Setting range: 0.0~50.0s
P01.03
The braking
current
before
starting
The inverter will carry out DC braking at the
braking current set before starting and it will
speed up after the DC braking time. If the DC
braking time is set to 0, the DC braking is invalid.
The stronger the braking current, the bigger the
braking power. The DC braking current before
starting means the percentage of the rated
current of the inverter.
The setting range of P01.03: 0.0~100.0%
The setting range of P01.04: 0.00~50.00s
0.0%
P01.04
The braking
time before
starting
0.00s
P01.05
ACC/DEC
selection
The changing mode of the frequency during
start-up and running.
0:Linear type
The output frequency increases or decreases
linearly.
0