Goodrive200A inverters Function parameters
43
Function
code
Name Detailed instruction of parameters
Default
value
different loads to meet various demands.
The setting range of P03.00:0~200.0
The setting range of P03.01: 0.000~10.000s
The setting range of P03.02:0.00Hz~P03.05
The setting range of P03.03:0~200.0
The setting range of P03.04: 0.000~10.000s
The setting range of P03.05:P03.02~P00.03(the
Max. output frequency)
P03.06
0~8 (corresponds to 0~2
8
/10ms) 0 ○
P03.07
Compensatio
n coefficient
of electro
motion slip
Slip compensation coefficient is used to adjust
the slip frequency of the vector control and
improve the speed control accuracy of the
system. Adjusting the parameter properly can
control the speed steady-state error.
Setting range:50~200%
100%
Compensatio
n coefficient
of braking
slip
100%
Current loop
percentage
coefficient P
Note:
1 These two parameters adjust the PI adjustment
parameter of the current loop which affects the
dynamic response speed and control accuracy
directly. Generally, users do not need to change
the default value.
2 Only apply to SVC control mode 0(P00.00=0).
Setting range:0~65535
1000 ○
P03.10
Current loop
integral
coefficient 1
Torque
setting
method
This parameter is used to enable the torque
control mode, and set the torque.
0:Torque control is invalid
1:Keypad setting torque(P03.12)
2:Analog AI1 setting torque(The inverter( ≤
15kW) can be set by the analog potentiometer on
the keypad and AI1 setting is not available for the
device which is 18.5kW or higer than 18.5kW)
3:Analog AI2 setting torque
4:Analog AI3 setting torque
5:Pulse frequency HDI setting torque
6:Multi-step torque setting
7:MODBUS communication setting torque
8~10:Reserved
Note: Setting modes 2~10, 100% corresponds to
0 ○