Goodrive200A inverters Function parameters
82
Function
code
Name Detailed instruction of parameters
Default
value
Modify
P10.29
The running
time of step
13
P10.(2n+1,1<n<17):0.0~6553.5s(min)
0.0s
P10.30
Multi-step
speed 14
0.0%
P10.31
The running
time of step
14
0.0s
P10.32
Multi-step
speed 15
0.0%
P10.33
The running
time of step
15
0.0s
P10.34
Simple PLC
0~7 step
ACC/DEC
time
Below is the detailed instruction:
Functio
n code
Binary bit Step
ACC/DE
C 0
ACC/DE
C 1
ACC/DE
C 2
ACC/DE
C 3
P10.34
BIT1
BIT0
0 00 01 10 11
BIT3
BIT2
1 00 01 10 11
BIT5
BIT4
2 00 01 10 11
BIT7
BIT6
3 00 01 10 11
BIT9
BIT8
4 00 01 10 11
BIT11
BIT10
5 00 01 10 11
BIT13
BIT12
6 00 01 10 11
BIT15
BIT14
7 00 01 10 11
P10.35
BIT1
BIT0
8 00 01 10 11
BIT3
BIT2
9 00 01 10 11
BIT5
BIT4
10 00 01 10 11
BIT7
BIT6
11 00 01 10 11
BIT9
BIT8
12 00 01 10 11
BIT11
BIT10
13 00 01 10 11
BIT13
BIT12
14 00 01 10 11
BIT15
BIT14
15 00 01 10 11
After the users select the corresponding
ACC/DEC time, the combined 16 binary bits will
change into decimal bit, and then set the
0x0000
P10.35
Simple PLC
8~15 step
ACC/DEC
time
0x0000