Goodrive200A inverters Function parameters
92
Function
code
Name Detailed instruction of parameters
Default
value
check 1: Hibernate as the feedback pressure﹥P24.04
Starting
frequency of
the
hibernation
0.00~P0.03(the Max. frequency)
10.00
Starting
pressure of
hibernation
0.0~3600.0s 5.0s ○
P24.06
0: Awake as the setting frequency﹥P24.07
1: Awake as the feedback pressure﹤P24.08
0 ◎
P24.07
0.00~P0.03(the Max. frequency)
20.00
Mini
hibernation
time
0.0~3600.0s 5.0s ○
P24.10
Valid
auxiliary
motor
P24.10~P24.12 can make three motors to form a
simple system of water supply.
P24.10 is used to select the valid auxiliary motor.
0: No auxiliary motor
1: Auxiliary motor 1 valid
2: Auxiliary motor 2 valid
3: Auxiliary motor 1 and 2 valid
Setting range of P24.10: 0.0~3600.0s
Setting range of P24.11: 0.0~3600.0s
0 ○
P24.11
auxiliary
motor 1
5.0s ○
P24.12