Goodrive200A inverters Function parameters
91
Function
code
Name Detailed instruction of parameters
Default
value
PID
reference
value
Display PID reference value
Range: -100.0~100.0%
●
P17.24
value
Display PID response value
Range: -100.0~100.0%
●
P17.25
Display the current power factor of the motor.
Range: -1.00~1.00
●
P17.26
Display the current running time of the inverter.
Range:0~65535min
●
P17.27
Simple PLC
and the
current step
of the
multi-step
speed
Display simple PLC and the current step of the
multi-step speed
Range: 0~15
●
P17.35
AC input
current
Display the input current in AC side.
Range: 0.0~5000.0A
●
P17.36
Display the output torque. Positive value is in the
electromotion state, and negative is in the power
generating state.
Range : -3000.0Nm~3000.0Nm
●
P17.37
Counting of
the motor
overload
0~100 (100 is OL1 fault)
●
P17.38
Wrong
download of
parameters
0.00~99.99 0.00 ●
P24 Group Water supply
P24.00
0: Disabled
1: Enabled
0 ◎
P24.01
Press
feedback
source
0: AI1 setting value (The inverter(≤15kW) can be
set by the analog potentiometer on the keypad
and AI1 setting is not available for the device
which is 18.5kW or higer than 18.5 kW)
1: AI2 setting value
2: AI3 setting value
3: HDI setting value
0 ○
P24.02
Hibernation
0: Hibernate as the setting frequency﹤P24.03 0 ◎